AutoMist

At the time of installation, the hood will receive an inspection sticker and will be re-inspected 90 days after installation.

The AutoMist system eliminates the need to perform manual cleaning on the entire commercial ventilation system. Restaurant Technologies technicians are training to perform inspections in accordance with NFPA 96.

While the AutoMist system is listed to the appropriate UL standard, it is not an integral part of the hood and fan units.
Where the system transitions into the hood a U.L. listed seal is used.

The restaurant operator is still required to remove and clean the filters, as well as areas considered to be outside the ventilation system. The filters should be cleaned when the AutoMist system is not scheduled to spray. A sticker indicating spray times is applied to the hood at the time of installation.

Restaurant Technologies provides on-site opportunities for local authorities to become familiar with the AutoMist system. A notification is also sent directly to the Authority Having Jurisdiction (AHJ) near the time of installation.

Restaurant Technologies will inspect the system at the frequency required by NFPA-96:

  • Systems serving Solid Fuel Cooking Operations are required to be inspected monthly.
  • Systems serving high-volume cooking operations such as 24 hour cooking or charbroiling are required to be inspected quarterly.
  • Systems serving low-volume cooking such as churches, day camps, seasonal businesses, and senior centers are required to be inspected semi-annually.

There is no regulation requiring the system to run. Compliance to NFPA-96 requires only that the ventilation system be inspected for cleanliness at a defined frequency, and that it be cleaned if found dirty.
Restaurant Technologies will inspect the system at the required frequency to ensure compliance. During those inspections, if it is found that the system had not been operating consistently since the prior inspection, Restaurant Technologies will correct the issue so that daily cleaning resumes.

NFPA 96 requires that the owner is presented a report that specifies areas that were inaccessible or not cleaned. NFPA 96 also requires that all areas not cleaned must be reported to the AHJ. Restaurant Technologies will provide the reports, per NFPA requirements.

The AutoMist system is listed to UL standard 73.

Restaurant Technologies will seal the single hood penetration with UL listed fire resistive plug.